Two light switches sit side by side on the trade counter. One is marked 10A, the other 10AX. They look alike, and a fitter asks the obvious question: what is the X for?

Quick Answer

In a switch rating, A covers tungsten, halogen and inductive loads, while X covers externally ballasted lamps, such as fluorescent luminaires and LED fittings with a separate driver. So 10AX describes the kind of lamp load the switch is rated for, not extra amps. Always check the marking against the load you are switching.

Browse Light Switches →

What the A and the X Each Promise

The clearest explanation comes from BEAMA, the trade body for the UK electrotechnical industry. Its May 2020 technical bulletin, Load ratings for manually operated functional switches, sets out what the letters mean on a switch marked to BS EN 60669-1.

  • A means a maximum 10A tungsten or halogen load, and a maximum 10A inductive load with a power factor of 0.6.
  • X means a maximum 10A externally ballasted lamp load. BEAMA's wording is rated current for externally ballasted LEDs and fluorescent luminaires.

So "10AX" is two promises written as one: the A load and the X load. The X does not add capacity. It adds a statement about a specific kind of lamp.

Marking What it states (per BEAMA) Example on TEO
10A 10AX 250V 10A for tungsten, halogen and inductive loads, plus 10A for externally ballasted lamps BG NBN12 Nexus Metal 1 gang 2 way plate switch
20A 10AX (dual marking) 20A for tungsten and halogen, but 10A for externally ballasted lamps BEAMA's own example of a dual mark
20A 20AX BG's grid module marking; BG states it handles inductive loads BG R13 Nexus Grid intermediate module

Why Lamp Type Needs Its Own Letter

A tungsten or halogen lamp is a simple resistive load. A fluorescent luminaire or an LED fitting with a separate driver is different: the ballast or driver sits between the switch and the lamp, and can draw a short, sharp surge at the moment of switching. That is a harder job for the contacts than a plain resistive load of the same current, which is why the standard gives the lamp type its own letter.

BEAMA also defines a self-ballasted lamp as a CFL or LED lamp where the control gear is built into the lamp, which is how most retrofit LED bulbs are made. The X is defined for externally ballasted lamps, so a 10AX mark does not by itself speak for every LED bulb on the shelf.

Trade Note: on a large LED installation with many drivers on a single switch, the combined surge adds up. Ask the driver or luminaire manufacturer for the maximum number of units per switch or circuit, rather than relying on the switch rating alone. For dimming, wattage ratings apply instead of AX, as we explain in our dimmer switch wattage guide and our trailing edge vs leading edge dimmer guide.


10AX Plate Switch or 20AX Grid Module?

The choice usually comes down to the system, not the rating alone.

  • Plate switches come as a finished faceplate. BG Nexus Metal switches such as the black nickel NBN12 are listed at 10A 10AX 250V and need a 16mm metal box. The BG Nexus Metal Brushed Steel range has the same style in a brushed steel finish.
  • Grid modules clip into a frame and plate you build yourself, which lets you mix 1-way, 2-way, intermediate, retractive and other modules in one plate. BG lists its grid switch modules at 20A 20AX, and the R13 intermediate module needs a 25mm minimum box depth. Browse them in the 20A 20AX grid modules collection.

If a grid plate needs a bell push or relay input, a momentary module is the right part, and our retractive switch guide explains how those work.


Mistakes That Cause Callbacks

  • Reading 10AX as 10A of anything. The marking describes lamp loads. A motor, a heater or an appliance is judged against the equipment's own instructions and the switch's other ratings.
  • Assuming 20AX is always double 10AX. BEAMA's dual-mark example shows 20A for one load type and 10A for another. Read the whole marking.
  • Ignoring driver inrush. A single LED fitting is easy. Thirty on one switch needs the manufacturer's guidance.
  • Forgetting box depth. Slim plate switches and grid modules need different depths, so check the product page before the first fix.

Frequently Asked Questions

Under BEAMA's guidance on switch load ratings, the X marks a maximum 10A externally ballasted lamp load, which covers fluorescent luminaires and LED fittings with a separate driver. The A marks a maximum 10A tungsten or halogen load and a 10A inductive load at a 0.6 power factor.
No. The marking describes lamp loads. Whether a switch suits a motor, a heater or another appliance depends on its other ratings and on the equipment's own instructions, so do not read 10AX as a general 10A rating.
Not necessarily. BEAMA's own example of a dual marking, 20A 10AX, gives 20A for tungsten and halogen but only 10A for externally ballasted lamps. BG's grid modules are marked 20A 20AX and BG describes them as handling inductive loads, so read the marking and the datasheet for the exact claim.
LED fittings with a separate driver are the externally ballasted type that the X refers to. BEAMA classes lamps with the driver built in as self-ballasted, so for many of those on one switch, check the manufacturer's guidance. Dimmers use their own wattage ratings rather than an AX marking.
Check the specification on the product page, for example 10A 10AX 250V on the BG NBN12, and the manufacturer's datasheet. Check the marking on the unit and its packaging when it arrives, before the first fix.

Match the Rating to the Load

BG 10AX plate switches and 20AX grid modules in stock across the main finishes, with trade pricing available.