Socket & Switch Height Rules: Part M Explained | TEO

An electrician wired a rear extension at the heights he'd used for fifteen years, and building control refused sign-off on the spot: the extension fell under Part M, and both socket and switch heights sat outside the accessible zone.

Quick Answer

Approved Document M sets an accessible zone of 450mm to 1200mm from finished floor level, measured to the centre of the switch or socket. It applies to new dwellings and Building Regulations-controlled work such as extensions. Old habitual heights, sockets low at the skirting and switches high at 1370mm, fall outside that band.

Browse Switches & Sockets at Trade Prices →

What Is the Accessible Zone Under Part M?

Approved Document M states that switches, socket outlets and similar controls should be positioned so their centre line falls between 450mm and 1200mm above finished floor level. The logic is straightforward: someone using a wheelchair, or anyone with restricted reach or mobility, needs to operate a switch or plug something in without bending to the floor or stretching overhead.

Accessory Type Part M Height (to Centre) Old Convention (Often Still Seen)
Socket outlets 450mm to 1200mm 150mm to 300mm
Light switches 450mm to 1200mm 1200mm to 1370mm
TV / data / telephone points 450mm to 1200mm Varies, often below 450mm
Consumer unit switches (where accessible use applies) 450mm to 1200mm Installer's choice, often higher
Measure to the centre, not the top or bottom of the faceplate. A standard single accessory plate is roughly 86mm tall, so the difference between measuring to the plate's edge versus its centre is enough to put an installation borderline on a strict inspection.

Where Does Part M Apply, and Where Doesn't It?

This is the point that causes the most confusion on site. Part M is a Building Regulations approved document, which means it applies where Building Regulations sign-off is required.

New-build dwellings
Applies throughout

Standard requirement across every room in a new dwelling, checked at Building Regulations sign-off.

Extensions & loft conversions
Applies to new floor area

Covers the newly created space, exactly as in the story above where an extension failed first-visit sign-off.

Like-for-like replacement
Not typically triggered

Swapping a faceplate in its existing position in an unaltered room isn't itself notifiable work.

That last point matters for landlords and property managers doing routine EICR remedial work: swapping a faceplate or replacing a faulty socket in its existing position generally doesn't require repositioning to meet Part M, because the work isn't itself notifiable under the regs that trigger the accessible-design requirement. Many electricians still choose to bring accessories into the 450mm to 1200mm band wherever practical, because it costs nothing extra during a rewire and future-proofs the installation.

Rewiring or fitting out to Part M standard? BG Evolve and BG Nexus switches and sockets are stocked across every finish, ready for same-day dispatch on stocked lines.

Shop British General Switches & Sockets →

Why Does This Matter Beyond Strict Compliance?

Outside strict Part M triggers, the accessible band is worth specifying as standard practice on any full rewire, HMO refurbishment, care home fit-out, or hotel guest room programme, properties where the occupant on any given day is unknown and may have limited mobility or be a wheelchair user. Getting it right at first fix avoids exactly the re-chasing cost in the story above, and it removes a recurring point of friction on care and assisted-living contracts where accessible design is scrutinised regardless of whether Part M is formally triggered.

How Do You Get It Right on Site?

  1. Confirm whether the job is Building Regulations-controlled before first fix: new build, extension and most conversions are; a straight like-for-like swap usually isn't.
  2. Mark out at 450mm and 1200mm before chasing, not after: moving a back box after plastering is the expensive mistake, not the height check itself.
  3. Measure to the accessory centre, using the back box centre line as your reference, not the top or bottom edge of the finished plate.
  4. Apply it consistently across a project even on rooms Part M doesn't strictly cover, so a hallway meeting the standard doesn't sit against a kitchen that doesn't.

Frequently Asked Questions

Approved Document M recommends switches and socket outlets be positioned between 450mm and 1200mm from finished floor level, measured to the centre of the accessory, so they are reachable by someone using a wheelchair or with limited reach.
Part M applies to new dwellings and to rooms subject to Building Regulations sign-off, such as extensions and some conversions. It is not usually a legal requirement for like-for-like replacement of an existing socket in an unaltered room, though many electricians apply the same heights as good practice regardless.
No, Approved Document M applies the same 450mm to 1200mm band to switches, socket outlets, and other controls such as TV points and telephone jacks. The guidance treats them as a single category of wall-mounted control that needs to be reachable without excessive bending or stretching.
Always measure to the centre line of the accessory, not the top or bottom edge of the faceplate. A standard single plate is roughly 86mm tall, so measuring from an edge instead of the centre can put an otherwise-compliant installation outside the band on inspection.
Generally no. Replacing a faulty socket in its existing position during routine remedial work isn't notifiable Building Regulations work, so Part M isn't formally triggered. Many electricians still reposition where practical, since it costs little extra during other works and avoids future non-compliance if the room is later altered.
It's strongly worth doing. Care homes, HMOs and hotel guest rooms house occupants whose mobility needs can change day to day, and accessible design is often scrutinised on these contracts regardless of whether Part M is formally triggered for a specific room. Applying the band consistently avoids inconsistent heights across a property.